ABB CI506-PNIO is a PROFINET IO RT communication interface and gateway module with two serial interfaces and one CANopen master interface for AC500 and S500 automation systems.

SKU: CI506-PNIOAlt SKU: CI506-PNIOMPN: 1SAP221500R0001
Price
List Price £626.00 ex VAT
Your Price (ex VAT) Save 15%
£532.10 15% OFF
You save £93.90 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £532.10
Trade pricing is personalised to your account

Manufacturer Lead Time

£532.10

Why Choose the ABB CI506-PNIO PROFINET Communication Interface Module?

The ABB CI506-PNIO, part number 1SAP221500R0001, is a PROFINET IO RT communication interface and gateway module designed for ABB AC500 and S500 automation systems. It combines 2 serial interfaces with 1 CANopen master interface, providing a flexible communication solution for integrating serial and CAN-based field devices into PROFINET networks.

The CI506-PNIO provides two configurable serial interfaces supporting RS232, RS422 and RS485 physical layers, together with a CAN interface supporting CAN 2A/CAN 2B and CANopen master communication. Two Ethernet ports with integrated switch functionality allow flexible PROFINET network connections and daisy-chain configurations.

Designed for decentralised automation architectures, the CI506-PNIO can be positioned close to connected field devices using the PROFINET network. It supports up to 10 S500 I/O modules, while its galvanically isolated bus interfaces help provide reliable communication between the industrial Ethernet network and connected field devices.

Key Advantages

  • PROFINET IO RT device and gateway for industrial automation networks.
  • Two configurable serial interfaces supporting RS232, RS422 and RS485.
  • CANopen master interface for integrating CAN-based field devices.
  • Supports CAN 2A and CAN 2B communication.
  • Two Ethernet ports with integrated switch functionality.
  • Supports flexible PROFINET network layouts and daisy chaining.
  • Can support up to 10 S500 I/O modules through the I/O bus.
  • Suitable for decentralised I/O and gateway applications within ABB AC500 automation systems.

Key Features

  • ABB AC500/S500 PROFINET communication interface module.
  • PROFINET IO RT communication.
  • 2 serial interfaces.
  • RS232, RS422 and RS485 physical-layer options.
  • ASCII serial communication protocol.
  • 1 CANopen master interface.
  • CAN 2A and CAN 2B support.
  • CANopen transmission rate up to 1 Mbit/s.
  • Support for up to 126 CANopen slaves.
  • 2 × RJ45 Ethernet connections with integrated switch.
  • 10/100 Mbit/s full-duplex Ethernet transmission.
  • Support for PROFINET RT Class 1 and acyclic communication services.
  • Minimum PROFINET bus cycle of 1 ms.
  • Up to 10 S500 I/O modules expandable through the I/O bus.
  • Two rotary switches for setting the I/O device identifier.
  • Diagnostic LEDs for system, Ethernet, serial and CAN communication status.

Reliable PROFINET, Serial and CAN Communication

The ABB CI506-PNIO provides a versatile gateway between PROFINET IO RT, serial devices and CAN-based equipment. Its two configurable serial interfaces can operate using RS232, RS422 or RS485, while the CAN interface provides CANopen master functionality for connecting compatible field devices and distributed automation components.

With two RJ45 Ethernet ports and integrated switching, the CI506-PNIO supports practical PROFINET network architectures and decentralised positioning near terminal devices. Its support for up to 10 S500 I/O modules also allows additional I/O capacity to be incorporated into a compact industrial communication station.

Typical Applications

  • PROFINET-based industrial automation systems.
  • Integration of serial field devices into PROFINET networks.
  • RS232, RS422 and RS485 device communication.
  • CANopen master applications.
  • Integration of CAN 2A and CAN 2B field devices.
  • Decentralised S500 I/O installations.
  • Machine and production-line automation.
  • AC500 PLC communication architectures.
  • Industrial gateway and fieldbus integration applications.

Technical Specifications

Tick the specs you need, then view products that match.

IP Rating IP20
Product Series ABB AC500
Device Type Communication / Function Module
Coil / Supply Voltage 20.4–28.8 V DC
Communication CANopen, PROFINET
Supported Protocols CANopen, PROFINET
Manufacturer ABB
Series AC500 / S500
Model CI506-PNIO
Product type PROFINET communication interface module
Product ID 1SAP221500R0001
Primary interface Ethernet
PROFINET protocol PROFINET IO RT
Ethernet interfaces 2 × RJ45
Ethernet transmission 10/100 Mbit/s full-duplex
Ethernet switch Integrated
Serial interfaces 2 × UART
Serial physical layers RS232, RS422, RS485
Serial protocol ASCII
CAN interface 1 × CAN
CAN protocol CANopen master
CAN transmission rate Up to 1 Mbit/s
CANopen slave capacity Up to 126
I/O bus expansion Up to 10 S500 I/O modules
Conformance class CC B
Process supply 24 V DC
Weight 0.200 kg
Terminal unit TU520-ETH
HS Code 85389091
Country of Manufacture Germany

Frequently Asked Questions

What is the ABB CI506-PNIO 1SAP221500R0001 used for?

The ABB CI506-PNIO is a PROFINET IO RT communication interface and gateway module used to integrate two serial interfaces and one CANopen master interface into ABB AC500 and S500 automation systems.

How many serial interfaces does the CI506-PNIO provide?

The CI506-PNIO provides 2 serial interfaces, with RS232, RS422 and RS485 available as physical-layer options.

Does the ABB CI506-PNIO support CANopen?

Yes. The CI506-PNIO includes 1 CANopen master interface and supports CAN 2A and CAN 2B communication with transmission rates up to 1 Mbit/s.

How many CANopen devices can the CI506-PNIO support?

The CI506-PNIO supports up to 126 CANopen slaves, subject to the applicable network configuration and system requirements.

How many S500 I/O modules can be connected to the CI506-PNIO?

The CI506-PNIO supports expansion with up to 10 S500 I/O modules through its I/O bus interface.