IOS/M08ITX-D1 IMO Remote I/O module, RS485 (HD) 8 A/D In (TC) Res: 0.1C

IOS/M08ITX-D1 IMO Remote I/O module, RS485 (HD) 8 A/D In (TC) Res: 0.1C

IMO IOS/M08ITX-D1 is an eight-channel thermocouple input remote I/O module supporting J, K, R, S, B, E, T and N sensors with 0.1 °C resolution, Modbus RTU RS-485 communications and a 10–30 V DC supply.

SKU: IOS/M08ITX-D1Alt SKU: IOSM08ITXD1MPN: IOS/M08ITX-D1
Price
List Price £367.17 ex VAT
Your Price (ex VAT) Save 15%
£312.09 15% OFF
You save £55.08 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £312.09
Trade pricing is personalised to your account

Manufacturer Lead Time

£312.09

Why Choose the IMO IOS/M08ITX-D1 Remote I/O Thermocouple Input Module?

The IMO IOS/M08ITX-D1 is a high-accuracy 8-channel thermocouple analogue input remote I/O module designed for industrial temperature measurement, process monitoring and distributed automation systems. As part of the IMO iOS Remote I/O series, it provides eight thermocouple input channels for integrating temperature sensors with compatible PLCs and industrial controllers.

The IOS/M08ITX-D1 supports a broad selection of thermocouple types, including J, K, R, S, B, E, T and N, together with millivolt input ranges for additional measurement flexibility. With 0.1 °C thermocouple resolution and accuracy of ±0.1% full scale, the module is well suited to applications requiring dependable multi-channel temperature acquisition.

Operating from a 10–30 V DC supply, the IOS/M08ITX-D1 communicates using Modbus RTU over an RS-485 half-duplex interface. Its slim DIN rail format, removable screw terminals and 2,000 V AC isolation make it suitable for distributed temperature monitoring within industrial machinery, process equipment and control panels.

Key Advantages

  • Dedicated 8-channel thermocouple input module for industrial temperature monitoring.
  • Supports J, K, R, S, B, E, T and N thermocouple types.
  • 0.1 °C thermocouple resolution for precise temperature measurement.
  • ±0.1% full-scale accuracy supports dependable process monitoring.
  • 2,000 V AC isolation helps provide reliable signal acquisition in industrial environments.
  • Integrated Modbus RTU communications over RS-485.
  • Removable screw terminals simplify installation, servicing and module replacement.

Key Features

  • IMO iOS Serial/Modbus Remote I/O series.
  • 8 thermocouple input channels.
  • Supports J, K, R, S, B, E, T and N thermocouples.
  • Additional ±50 mV, ±100 mV, ±500 mV and ±1 V input ranges.
  • 0.1 °C or 0.001 mV resolution.
  • Input impedance greater than 10 MΩ.
  • ±0.1% full-scale accuracy.
  • Modbus RTU communications.
  • RS-485 half-duplex serial interface.
  • 10–30 V DC operating supply.
  • 2,000 V AC isolation for 60 seconds.
  • Removable screw terminals for convenient field wiring.

Accurate Multi-Channel Temperature Monitoring for Industrial Automation

Thermocouples are widely used for industrial temperature measurement because they provide robust sensing across a broad range of process and machinery applications. The IMO IOS/M08ITX-D1 provides eight dedicated channels in a compact module, allowing multiple temperature measurement points to be integrated into a distributed control system without requiring individual analogue input modules for every sensor.

The module's support for multiple thermocouple types provides flexibility when working with different temperature ranges and industrial processes. Modbus RTU communications allow the IOS/M08ITX-D1 to be positioned remotely from the main controller, while isolated inputs and high input impedance help provide dependable measurement in industrial environments.

Typical Applications

  • Industrial thermocouple temperature monitoring.
  • Industrial ovens, furnaces and heating systems.
  • Process and production machinery.
  • Plastics, packaging and manufacturing equipment.
  • Food and beverage process temperature monitoring.
  • HVAC and thermal control systems.
  • Distributed PLC and remote I/O installations.
  • OEM machinery and industrial control panels.

Technical Specifications

Tick the specs you need, then view products that match.

Supported Protocols Modbus RTU
Communication RS485
Current 8 A
Manufacturer IMO Precision Controls
Series iOS Remote I/O
Model IOS/M08ITX-D1
Product type Thermocouple analogue input remote I/O module
Number of inputs 8 thermocouple input channels
Supported thermocouples J, K, R, S, B, E, T, N
Voltage input ranges ±50 mV, ±100 mV, ±500 mV, ±1 V
Resolution 0.1 °C or 0.001 mV
Accuracy ±0.1% full scale
Input impedance >10 MΩ
Supply voltage 10–30 V DC
Typical power requirement 30 mA at 24 V DC
Isolation 2,000 V AC for 60 seconds
Communication protocol Modbus RTU
Communication interface RS-485 half duplex
Default baud rate 38,400 baud
Default communication format No parity, 8 data bits, 1 stop bit
Default Modbus ID 1
Supported Modbus commands 1, 2, 3, 4, 5, 6, 8, 15, 16
Terminal type Removable screw terminals
Dimensions (W × H × D) 17.5 × 100 × 120 mm
Weight 150 g
Operating temperature -10 to +60 °C
Storage temperature -40 to +85 °C
Relative humidity 5–95%, non-condensing
HS Code 8538909190
Country of Manufacture Italy

Frequently Asked Questions

What is the IMO IOS/M08ITX-D1 used for?

The IOS/M08ITX-D1 is an 8-channel thermocouple input remote I/O module used to acquire temperature measurements from industrial thermocouples and transmit the data to a compatible automation controller over a Modbus network.

Which thermocouple types does the IOS/M08ITX-D1 support?

The module supports J, K, R, S, B, E, T and N thermocouple types, providing flexibility for a wide variety of industrial temperature measurement applications.

What resolution does the IOS/M08ITX-D1 provide?

The IOS/M08ITX-D1 provides a thermocouple measurement resolution of 0.1 °C and a voltage measurement resolution of 0.001 mV.

What communication interface does the IOS/M08ITX-D1 use?

The module uses Modbus RTU communications over an RS-485 half-duplex interface, with default communications configured for 38,400 baud.

What supply voltage does the IOS/M08ITX-D1 require?

The IOS/M08ITX-D1 operates from a 10–30 V DC supply and typically requires approximately 30 mA at 24 V DC.

Reliable Temperature I/O for Industrial Control Systems

IMO iOS Remote I/O modules provide machine builders and automation engineers with flexible distributed I/O, combining accurate temperature measurement, isolated signal acquisition, Modbus communications and removable terminals for dependable industrial integration.