Call us now on: 01706 242050 or email [email protected]

SK827041-AM ek550-40-11-230-240v50hz ABB Contactor

SKU
EK550-40-11-230-240V
Special Price £2,739.79 £2,283.16 Regular Price £3,913.99

ABB EK550-40-11-230-240V50HZ Cont-SK827041-AM 4 main poles Dimensions
Product Net Width: 300 mm
Product Net Depth: 270 mm
Product Net Height: 225 mm
Product Net Weight: 17.5 kg Technical
Number of Main Contacts NO: 4
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Rated Operational Voltage: Main Circuit 1000 V
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors q = 40 °C 800 A
Rated Operational Current AC-1 (Ie):
(690 V) 55 °C 650 A
(690 V) 40 °C 800 A
(690 V) 70 °C 575 A
Rated Operational Current AC-3 (Ie):
(1000 V) 55 °C 175 A
(690 V) 55 °C 550 A
(220 / 230 / 240 V) 55 °C 550 A
(440 V) 55 °C 550 A
(440 V) 55 °C Q55C415V:550 A
(380 / 400 V) 55 °C 550 A
(500 V) 55 °C 550 A
Rated Operational Power AC-3 (Pe):
(500 V) 400 kW
(1000 V) 250 kW
(690 V) 500 kW
(220 / 230 / 240 V) 160 kW
(380 / 400 V) 280 kW
(440 V) 315 kW
(415 V) 315 kW
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1: 8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1: 10 x Ie AC-3
Short-Circuit Protective Devices: gG Type Fuses 800 A
Rated Short-time Withstand Current (Icw):
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 3700 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 5300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 5500 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 3000 A
Maximum Electrical Switching Frequency:
AC-3 300 cycles per hour
AC-1 300 cycles per hour
AC-2 / AC-4 120 cycles per hour
Rated Insulation Voltage (Ui):
acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage (Uimp): 8 kV
Mechanical Durability: 5 million
Maximum Mechanical Switching Frequency: 3600 cycles per hour
Coil Operating Limits: (acc. to IEC 60947-4-1) Uc (at θ ≤ 70 °C) °C
Rated Control Circuit Voltage (Uc):
60 Hz 110 … 120 V
50 Hz 110 V
Coil Consumption:
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 4000 V·A
Holding at Max. Rated Control Circuit Voltage 50 Hz 140 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 3500 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 125 V·A
Operate Time:
Between Coil Energization and NO Contact Closing 30…60 ms
Between Coil De-energization and NO Contact Opening 13…23 ms
Between Coil De-energization and NC Contact Closing 10…20 ms
Between Coil Energization and NC Contact Opening 25…55 ms
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Connecting terminals (delivered in open position) Main poles: Flat type c/w screws and bolts
Terminal Type: Screw Terminals

. EK550 4-pole contactors are mainly used for controlling non-inductive loads and for controlling power circuits up to 1000 V AC and 600 V DC, EK1000 up to 1000 V AC. They are of the block type design with 4 main poles.
More Information
Manufacturer ABB
kW Rating 250KW, 280KW, 315KW, 400KW
Inbuilt Aux 1 N/O, 1 N/C
Alternative Product SKU SK827041-AM
Manufacturer Part Number EK550-40-11-230-240V
Product Lead Time Contact us for a delivery time before you order
Links Click here for link to ABB website info (opens in new tab)
Write Your Own Review
You're reviewing:SK827041-AM ek550-40-11-230-240v50hz ABB Contactor

Latest News

5 top benefits of energy monitoring equipment for your business

5 top benefits of energy monitoring equipment for your business

April 16, 2024 Read full
Why choose the Rittal VX25 range for your operations?

Why choose the Rittal VX25 range for your operations?

March 26, 2024 Read full
4 key avenues to help increase efficiency in your operations

4 key avenues to help increase efficiency in your operations

March 21, 2024 Read full
4 common challenges with factory automation (and their solutions)

4 common challenges with factory automation (and their solutions)

February 27, 2024 Read full