Call us now on: 01706 242050 or email [email protected]

1sda068622r1 xt4v 160 ekip lsi in=63a 4 pole abb mccb

SKU
1SDA068622R1
Email for pricing and availability

XT4V 160 Ekip LSI In=63A 4p F F C.BREAKER TMAX XT4V 250 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-I R 63 A

Dimensions
Product Net Width: 140 mm
Product Net Height: 160 mm
Product Net Depth: 82.5 mm
Product Net Weight: 3.5 kg

Additional Information
Circuit Breaker Type to be Associated: Power distribution
Electrical Durability:
120 cycles per hour
8000 cycle
Mechanical Durability:
Nr. Operations 240 cycles per hour
Nr. Operations 25000 cycle
Number of Poles: 4
Opening Time:
CB with SOR 15 ms
CB with UVR 15 ms
Product Main Type: SACE Tmax XT
Product Name: Moulded Case Circuit Breaker
Product Type: CB
Rated Current (In): 63 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Insulation Voltage (Ui): 1000 V
Rated Operational Voltage: 690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics):
(220 V AC) 200 kA
(220 V AC) 200 kA
(380 V AC) 150 kA
(415 V AC) 150 kA
(440 V AC) 150 kA
(500 V AC) 70 kA
(690 V AC) 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(220 V AC) 200 kA
(230 V AC) 200 kA
(380 V AC) 150 kA
(415 V AC) 150 kA
(440 V AC) 150 kA
(500 V AC) 70 kA
(690 V AC) 25 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Release Type: EL
Standards: IEC
Sub-type: XT4
Terminal Connection Type:
Fixed Circuit-Breakers
Front
Version: F

More Information
Product Image For Illustration Purposes Only
Manufacturer ABB
Manufacturer Part Number 1SDA068622R1
Number of Poles 4 pole
Amperage 63A
Alternative Product SKU XT4V 160 Ekip LSI In=63A 4p F F
Product Lead Time Please contact us for a delivery time
Links Click here for link to ABB website info (opens in new tab)
Write Your Own Review
You're reviewing:1sda068622r1 xt4v 160 ekip lsi in=63a 4 pole abb mccb

Latest News

5 top benefits of energy monitoring equipment for your business

5 top benefits of energy monitoring equipment for your business

April 16, 2024 Read full
Why choose the Rittal VX25 range for your operations?

Why choose the Rittal VX25 range for your operations?

March 26, 2024 Read full
4 key avenues to help increase efficiency in your operations

4 key avenues to help increase efficiency in your operations

March 21, 2024 Read full
4 common challenges with factory automation (and their solutions)

4 common challenges with factory automation (and their solutions)

February 27, 2024 Read full